3000GPM 125PSI Single Stage Double Suction Centrifugal Pump For Firefighting

Product Details

Place of Origin: China

Brand Name: CNP NM FIRE

Certification: NFPA20/UL/FM/EN12845/CCCF

Model Number: SCF300-250-490 (12x10")

Payment & Shipping Terms

Minimum Order Quantity: 1set

Price: Negotiation

Packaging Details: Export Packing

Delivery Time: 30-45 Working Days

Payment Terms: L/C, T/T

Get Best Price
Highlight:

diesel fire pump

,

fire fighting water pump

Certification::
UL/FM/NFPA20
Flow::
3000GPM
RPM:
1800 (60Hz)
Engine::
DE MAAS & NM Fire
Control Panel::
Tornatech (UL/FM)
Head:
125PSI
Certification::
UL/FM/NFPA20
Flow::
3000GPM
RPM:
1800 (60Hz)
Engine::
DE MAAS & NM Fire
Control Panel::
Tornatech (UL/FM)
Head:
125PSI
3000GPM 125PSI Single Stage Double Suction Centrifugal Pump For Firefighting

UL/FM/NFPA20 Certification 3000GPM @ 125PSI Centrifugal Fire Pump Capacity For Firefighting Applications

 

Horizontal Split Case
The protection of life is not a matter for compromise
This is particularly true for fire protection systems where they are only as strong as their 'weakest link' and compromise may result in avoidable loss of life or property. That is why NM fire pumps are designed specifically for the very particular needs of fire protection and are approved by most of the major fire protection bodies around the world. By selecting an approved NM Fire Pump as part of an approved system and maintained in accordance with standards such as NFPA 20, you can sleep easy knowing that you have chosen the best you can get.

 

KEY FEATURES

  • Complete compact unit
  • Horizontal
  • Tailored to the customer's required standards and specifications
  • Configuration for NFPA20 / FM / UL up to 4000 US gpm
  • Good suction characteristics, also with higher speeds
  • Practically no limitations on flow
  • Less wear and tear influences
  • Easy maintenance without interfering on piping / driver
  • Select Models Available in alternate materials with FM approval

 

Parameters:

 

HEAD PUMP MODEL SPEED MAX SHAFT POWER
PSI FEET METER RPM HP KW
125 289 88 SCF300-250-490
(12x10")
1800
(60Hz)
423 315.1

 

 

Each pump shall have a circulation relief valve listed for the fire pump service installed and set below the shutoff pressure at minimum expected suction pressure. Exception: This rule shall not apply to engine-driven pumps for which engine cooling water is taken from the pump discharge.

 

 

Performance Ranges:

 

 

UL:

 

 Q: 500-4000GPM  H:100-190PSI

 

FM:

 

 Q: 500-4000GPM  H:100-190PSI

 

CCCF:

 

 Q:20-500L/S  H:0.42-2.0Mpa

 

NFPA20:

 

 Q: 300-8000GPM  H:60-300PSI

 

 

 

Product Type:

 

Diesel engine driven fire pump sets with air cooling & water cooling

 

NFPA20 Package

 

 

Advantage:

 

First-Class international technical standards.

 

CNP NM FIRE is the first member of NFPA from China pump's manufacturers.and won the UL,FM international fire certification for fire pump products.

 

 

Service:

 

1. To supply high-quality products with reasonable prices in food additive industry.
2. To follow orders and arrange shipping in time, providing complete documents
for Customs clearance according to different export policies in different countries.